Rated current In (A): 80A, 100A, 125A
Rated voltage Ue (V): DC60/80V, AC230/240/400/415V
Poles: 1P, 2P, 3P, 4P
Breaking capacity (Icu): 4.5kA, 10kA
Certifications: CCC, CB, CE, TUV
| Rated Voltage (Ue) | DC60/80V(1P), AC230/240V(1P ,2P), AC400/415V(3P,4P) |
| Rated Current (In) | 80A, 100A, 125A |
| Tripping Characteristic | / |
| Tripping curve | Type C |
| Rated Breaking Capacity (Icn) | / |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | AC Icu :4.5kA , DC Icu :10kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | AC Ics: 4.5kA , DC Ics :10kA |
| Number of Poles | 1P, 2P, 3P, 4P |
| Standards and Certificates | ·CCC, CB, CE, TUV ·GB/T14048.2、IEC 60947-2 |
| Environmental Requirements | RoHS |
| Rated Insulation Voltage | 500V |
| Rated Impulse Withstand Voltage | 4kV |
| Rated Frequency | 50/60Hz |
| Wiring | ·Adopt tunnel type wiring ·Connection capability: 1mm² to 50 mm² ·Connection screw M6, Torque: 3.0N.m |
| Mechanical Life | 8500 times |
| Electrical Life | 1500 times |
| Working Condition | ·Ambient temperature: -25℃~+75℃ ·Storage temperature: -40℃~+80℃ ·Relative air humidity ≤95% ·Resistance to heat and humidity: in case of ambient temperature 55℃ ·Altitude ≤2000m. In case of use at higher altitude, it may be derated according to the requirements of small-sized circuit breaker of the company. Refer to GB/T 20645 Specific Environmental Condition Technical Requirements of Low-voltage Apparatuses for Plateau. ·Pollution degree: 3 ·Protection Degree: IP20 ·Protection grade for device which is installed in distribution box: IP40 ·Working site without obvious vibration and shock |
| Isolation function | ·Practical breaking instructions ·View window within the green identification said contact in the off position |
·Quantity(1P product:12PCS/box,1PN/2P product:6PCS/box,3P product:4 PCS/box,3PN/4P product: 3PCS/box)
·Packing boxes of products should be stored in the air circulation and relative humidity is not more than 95% and the temperature is not higher than + 75 ℃,not less than - 25 ℃ in the air around without acid, alkali or other corrosive gases stored in the warehouse. In the above conditions, the storage period since the production date not more than three years.
Quality Controls
Delivery Guarantees
Made in China
Transaction Visualization
No Worries After-sales
Professional Experience