Rated current In (A): 400A
Rated working voltage Ue: DC750V
Coil control voltage Uc (V): DC12V/24V
|
Rated current (A) |
400A |
|
|
Rated voltage Ue (V) |
DC750V |
|
|
Main Circuit Polarity |
Polarized |
|
|
Insulation voltage Ui (V) |
DC1000V |
|
|
Control Coil |
Rated voltage Ui (V) |
DC12V, DC24V |
|
Operating Voltage |
75%~110% Uc |
|
|
Drop-out Voltage |
10%~60% Uc |
|
|
Coil Polarity |
Polarized |
|
|
Turn-on Time (20°C, Rated Voltage) |
≤30ms |
|
|
Turn-off Time (20°C) |
≤10ms |
|
|
Coil Power Consumption (20°C) |
Pick-up: 45W; Hold: 4.5W |
|
|
Installation position torque |
M5 screw(3~4N.m) |
|
|
Wiring terminal torque |
M6 screw(6~8N.m) |
|
|
Certificates |
/ |
|
|
Mechanical life |
200000 times, frequency 3600 times/h |
|
|
Electrical life (Make 0.6s/Break 5.4s) |
DC750V 400A |
1000times |
|
Maximum breaking current |
DC750V 3000A |
Once |
|
Short-circuit withstand current |
3000A 600ms 1200A 30s 600A 20min |
|
|
Contact Resistance (at Rated Current) |
≤0.2mΩ |
|
|
Insulation resistance |
1000mΩ, DC1000V |
|
|
Dielectric Strength |
·Between open contacts: AC3000V for 1min (leakage current ≤1mA) ·Between contacts and coil: AC3000V for 1min (leakage current ≤1mA) |
|
|
Shock Resistance |
·Stability: 20g (ON state), 10g (OFF state) (half-sine pulse: 11ms, detection time 10μs) ·Destruction: 50g (half-sine pulse: 6ms) |
|
|
Vibration Resistance |
10~500Hz 5g |
|
|
Product Weight |
Approx. 730g |
|
|
Normal Working Environment |
·Operating environment:-40~85℃ ·Operating humidity:5%~95% ·Pollution level:3 |
|
|
Installation Mode |
Screw mounting |
|
|
Environmental Compliance |
Comply with the RoHS directives |
|


Quality Controls
Delivery Guarantees
Made in China
Transaction Visualization
No Worries After-sales
Professional Experience