NDM3Z-250V Series DC MCCB, Nader - Image 1
NDM3Z-250V Series DC MCCB, Nader - Image 2
NDM3Z-250V Series DC MCCB, Nader - Image 3
NDM3Z-250V Series DC MCCB, Nader - Image 4
NDM3Z-250V Series DC MCCB, Nader - Thumbnail 1
NDM3Z-250V Series DC MCCB, Nader - Thumbnail 2
NDM3Z-250V Series DC MCCB, Nader - Thumbnail 3
NDM3Z-250V Series DC MCCB, Nader - Thumbnail 4

NDM3Z-250V Series DC MCCB, Nader

Rated current In (A): 125A, 140A, 160A, 180A, 200A, 225A, 250A

Rated voltage Ue (V): DC1000/1500V

Poles: 2P, 3P

Rated ultimate short-circuit breaking capacity Icu (kA): 20kA

Certifications: CCC, CB, CE, TUV

Technical parameters:

Rated current of frame Inm (A)

250A

Rated Voltage (Ue) (V)

DC1000V

DC1500V

Rated Current (In) (A)

125A, 140A, 160A, 180A, 200A, 225A, 250A

Rated Insulation Voltage Ui (V)

1500V

Rated impulse withstand voltage Uimp (V)

12000V

Tripping Characteristics

/

Number of Poles

2P

3P

Rated limit short-circuit breaking capacity level

/

Rated limit short-circuit breaking capacity Icu (kA)

20kA

20kA

Rated operating short-circuit breaking capacity Ics (kA)

16kA

16kA

Rated Frequency (Hz)

50/60Hz

Standards and Certificates

·CCC, TUV, CE

·GB/T 14048.1, GB/T 14048.2, IEC 60947-1, IEC 60947-2

Maintenance-free life

10000 times

Maintainable life

20000 times

Electrical Life

2000 times

Flashover distance(mm)

≤50

Wiring

·Wiring mode: /

·Thread diameter: M8 (Torque value: 12N.m), M4 (Torque value: 2.4N.m)

·Connection capacity:

50mm² (125A, 140A), 70mm² (160A), 95mm² (180A, 200A, 225A), 120mm² (250A)

Normal Working Environment

·Ambient Temperature: -35℃~+70℃

·Storage Temperature: -40℃~+75℃

·Altitude: ≤2500m

·Environmental Requirements: RoHS

·Relative Humidity: The relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higher relative humidity is allowed at a lower temperature.

·The product can withstand the effects of wet air, salt mist and oil mist.

·Pollution Level: 3

·Protection class: IP20

Isolation Function

·Installation Category:

The installation category of the circuit breaker connected to the main loop is:Ⅲ(power distribution and control level);

The installation category of the circuit breaker not connected to the main loop is:Ⅱ(load level).

·Installation Environment:

The product should be installed in places that are free from explosive media, media corrosive to metal, insulation damaging gas, and conductive dust, which should be also avoided from snow and rain.

Tripping characteristic curve

Outline and installation dimension

Packing and depositing:

·Minimum packaging quantity: 1 piece/box.

·The packaged products should be stored in a warehouse with the ambient temperature of-40℃~75 ℃ and the corresponding relative humidity below 80% without acidic, alkali or other corrosive gas in the surrounding air. Under the conditions above, the storage period shall be no more than 36 months since the manufacturing date.

Quality Controls

Delivery Guarantees

Made in China

Made in China

Transaction Visualization

No Worries After-sales

Professional Experience