NDM3Z-125 Series DC MCCB, Nader

Rated current In (A): 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A

Rated voltage Ue (V): DC500/750/1000V

Poles: 2P, 3P, 4P

Rated ultimate short-circuit breaking capacity Icu (kA): 20kA

Certifications: CCC, CB, CE, TUV

Technical parameters:

Rated current of frame Inm (A)

125A

Rated Voltage (Ue) (V)

DC500V

DC750V

DC1000V

Rated Current (In) (A)

16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A

Rated Insulation Voltage Ui (V)

1000V

Rated impulse withstand voltage Uimp (V)

8000V

Tripping Characteristics

/

Number of Poles

2P

3P

4P

Rated limit short-circuit breaking capacity level

/

Rated limit short-circuit breaking capacity Icu (kA)

20kA

20kA

20kA

Rated operating short-circuit breaking capacity Ics (kA)

20kA

20kA

20kA

Rated Frequency (Hz)

50/60Hz

Standards and Certificates

·CCC, TUV, CE

·GB/T 14048.1, GB/T 14048.2, IEC 60947-1, IEC 60947-2

Maintenance-free life

20000 times

Maintainable life

40000 times

Electrical Life

5000 times

Flashover distance(mm)

≤50

Wiring mode

/

J0

J0, J1, J2

Thread diameter

M8 (Torque value: 12N.m), M4 (Torque value: 2.4N.m)

Connection capacity

2.5mm² (16A, 20A), 4.0mm² (25A), 6.0mm² (32A), 10mm² (40A, 50A), 16mm² (63A), 25mm² (80A), 35mm² (100A), 50mm² (125A)

Normal Working Environment

·Ambient Temperature: -35℃~+70℃

·Storage Temperature: -40℃~+75℃

·Altitude: ≤2500m

·Environmental Requirements: RoHS

·Relative Humidity: The relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higher relative humidity is allowed at a lower temperature.

·The product can withstand the effects of wet air, salt mist and oil mist.

·Pollution Level: 3

·Protection class: IP20

Isolation Function

·Installation Category:

The installation category of the circuit breaker connected to the main loop is:Ⅲ(power distribution and control level);

The installation category of the circuit breaker not connected to the main loop is:Ⅱ(load level).

·Installation Environment:

The product should be installed in places that are free from explosive media, media corrosive to metal, insulation damaging gas, and conductive dust, which should be also avoided from snow and rain.

Tripping characteristic curve

Outline and installation dimension

Packing and depositing:

·Minimum packaging quantity: 1 piece/box.

·The packaged products should be stored in a warehouse with the ambient temperature of-40℃~75 ℃ and the corresponding relative humidity below 80% without acidic, alkali or other corrosive gas in the surrounding air. Under the conditions above, the storage period shall be no more than 36 months since the manufacturing date.