Used in the telecom, nominal discharge current is 20kA, max. discharge current is 50kA, and total Maximum discharge current is 150kA.
| SPD type | 1+2 |
| Network | 230/400 V 3-phase+N |
| AC system | TT-TNS |
| Max.AC operating voltage | 320 Vac |
| Temporary Over Voltage (TOV) Characteristics - 5 sec.Without disconnection | 335 Vac withstand |
| Temporary Over Voltage (TOV) Characteristics - 120 mnWithout disconnection or with safety disconnection | 440 Vac disconnection |
| Temporary Over Voltage N/PE (TOV HT) Without disconnection or with safety disconnection | 1200 V/300A/200 ms withstand |
| Temporary Over Voltage N/PE (TOV HT) | 1200 V/300A/200 ms withstand |
| Nominal discharge current15 x 8/20 µs impulses | 20kA |
| Max. discharge currentmax. withstand @ 8/20 µs by pole | 50kA |
| Total Maximum discharge currentmax. total withstand @ 8/20 µs | 150kA |
| Impulse current by polemax. withstand 10/350µs by pole | 12.5 kA |
| Total lightning currentmax. total withstand @ 10/350µs | 50 kA |
| Specific energy by polemax. withstand 10/350 µs | 40 kJ/ohm |
| Protection mode(s) | L/N and N/PE |
| Protection level@ In (8/20µs) and @ 6 kV (1, 2/50 µs) | 1.6kV |
| Protection level N/PE @ In (8/20µs) and @ 6 kV (1, 2/50 µs) | 1.5kV |
| Residual voltage L/N at 5 kA@ 5 kA (8/20µs) | 1.2kV |
| Protection level N/PE at 5 kA @ 5 kA (8/20µs) | 1.2kV |
| Protection level N/PE | 5000A |
| Residual voltage L/N at 5 kA | Common/Differential mode |
| Protection level N/PE at 5 kA | 2000 V |
| Admissible short-circuit current | 25000 A |