Used in solar energy, nominal discharge current (In) is 20kA, max. discharge current (Imax) is 50 kA,and impulse current by pole (Iimp) is 12.5kA.

SPD type 1+2
Max. AC operating voltage (Uc) 320 Vac
Temporary Over Voltage (TOV) Characteristics - 5 sec. (UT) 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn (UT) 440 Vac disconnection
Residual Current (Ipe) <1 mA
Nominal discharge current (In) 20kA
Max. discharge current (Imax) 50 kA
Impulse current by pole (Iimp) 12.5kA
Specific energy by pole (W/R) 40 kJ/ohm
Protection level (up) 1.6 kV
Residual voltage L/N at 5 kA (Up-5kA) 1.2kV
Admissible short-circuit current (Isccr) 50 000 A